Data size (param06) – Yaskawa MP920 Communications Module User Manual
Page 237

Appendix A System Functions
A.1.3 Parameter Details
A-8
1. Read/write request for coils or relays: Set the leading bit address of the data.
2. Continuous read/write request for registers: Set the leading word address of the data.
3. Discontinuous read/write request for registers: Set the leading word address of the
address table.
The following data address setting range is used for no-protocol transmissions.
Data Size (PARAM06)
Set the size (number of bits or words) of the data to be read or written.
The setting range differs according to the function code.
33H
MELSEC random buffer write
0 to 32767 (0 to 7FFFH)
2
(cont’d)
Function
Code
Function
Data Address Setting Range
215IF, 218IF,
MECHATROLINK
217IF, Serial
F#
Function
Data Address Setting Range
-
-
0 to 32767 (0 to 7FFFH)
Function
Code
Function
Data Address Setting Range
215IF, 218IF
217IF, Serial
MECHATROLINK
00H
Not used.
Not valid.
01H
Coil status read
Bits 1 to 2000 (1 to 07D0H)
02H
Input relay status read
Bits 1 to 2000 (1 to 07D0H)
03H
Holding register read
Words 1 to 125 (1 to 007DH)
04H
Input register read
Words 1 to 125 (1 to 007DH)
05H
Single coil status change
Not valid.
06H
Single holding register write
Not valid.
07H
Not used.
Not valid.
08H
Loopback test
Not valid.
09H
Holding register read (extended)
Words 1 to 508 (1 to
1FCH)
Not valid.
Words 1 to 252 (1 to
00FCH)
0AH
Input register read (extended)
Words 1 to 508 (1 to
1FCH)
Not valid.
Words 1 to 252 (1 to
00FCH)
0BH
Holding register write (extended)
Words 1 to 507 (1 to
1FBH)
Not valid.
Words 1 to 252 (1 to
00FBH)
0CH
Not used.
Not valid.
0DH
Discontinuous holding register read
(extended)
Words 1 to 508 (1 to
1FCH)
Not valid.
Words 1 to 252 (1 to
00FCH)
0EH
Discontinuous holding register write
(extended)
Words 1 to 254 (1 to
0FEH)
Not valid.
Words 1 to 126 (1 to
007EH)
0FH
Multiple coil status change
Bits 1 to 800 (1 to 0320H)
10H
Multiple holding register write
Words 1 to 100 (1 to 0064H)