Remote cpu number (param07), Coil offset (param08), Input relay offset (param09) – Yaskawa MP920 Communications Module User Manual
Page 238: Input register offset (param10), Holding register offset (param11)

A.1 SEND MESSAGE Function (MSG-SND)
A-9
A
The following setting range is used for no-protocol transmissions.
Remote CPU Number (PARAM07)
Set the remote CPU number.
When the transmission destination is the CP-317, CP-9200SH, or CP-9200, set 1 or 2. When
the destination is the CP-3500H, set 1, 2, 3, or 4. In other cases, set 0.
Coil Offset (PARAM08)
Set the offset word address of the coils.
This parameter is valid when the function code is 01H, 05H, or 0FH.
Input Relay Offset (PARAM09)
Set the offset word address of the input relays.
This parameter is valid when the function code is 02H.
Input Register Offset (PARAM10)
Set the offset word address of the input registers.
This parameter is valid when the function code is 04H or 0AH.
Holding Register Offset (PARAM11)
Set the offset word address of the holding registers.
This parameter is valid when the function code is 03H, 06H, 09H, 0BH, 0DH, 0EH, or 10H.
31H
MELSEC fixed buffer communications
Words 1 to 507 (1 to
1FBH)
Not valid.
Not valid.
32H
MELSEC random buffer read
Words 1 to 508 (1 to
1FCH)
Not valid.
Not valid.
33H
MELSEC random buffer write
Words 1 to 508 (1 to
1FCH)
Not valid.
Not valid.
(cont’d)
Function
Code
Function
Data Address Setting Range
215IF, 218IF
217IF, Serial
MECHATROLINK
Data Address Setting Range
217IF
218IF
215IF
No-protocol 1
Words 1 to 254
Words 1 to 510
Words 1 to 510
No-protocol 2
Bytes 1 to 508
Bytes 1 to 1020
Bytes 1 to 1020