5.7 CP-215 Repeaters

5-45

5

„

Environmental Conditions

„

Structure

„

Maximum Number of Repeaters that Can Be Connected

The maximum number of Repeaters that can be connected is as follows:

• For CP-215 communications: 8 Repeaters or less (Total transmission distance: 12 km

max.)

• For CP-216 communications : 2 Repeaters or less

(Total transmission distance for 1 Repeater: 600 m max. at 4 Mbps)
(Total transmission distance for 2 Repeaters: 350 m max. at 4 Mbps)

Item

Specifications

Operating Temperature

0 to 55

°

C

Operating Humidity

5 to 95%RH (no condensation)

Storage Temperature

-25 to + 85

°

C

Storage Humidity

5 to 95% (no condensation)

Vibration Resistance

Conforming to JIS B 3502:
10 to 150 Hz with single-amplitude of 0.075 mm
57 to 150 Hz with fixed acceleration of 9.8 m/s

2

(1G)

Shock Resistance

Conforming to JIS B 3502:
Peak acceleration of 147 m m/s

2

(15G) twice for 11 ms each

in the

±X, ±Y, and ±Z directions

Ground

Ground to 100

Ω max.

Item

Specifications

Ground

Panel mount type (mounting screws: M5

× 4)

Dimensions

69.8

× 262.4 × 120.2 mm (W × H × D)

Cooling Method

Natural cooling

Mass

1.6 kg