Pro-typ (communications protocol), Cir-no (line no.), Ch-no (channel no.) – Yaskawa MP920 Communications Module User Manual
Page 240: Param (parameter list leading address)

A.1 SEND MESSAGE Function (MSG-SND)
A-11
A
PRO-TYP (Communications Protocol)
PRO-TYP specifies the communications protocol.
When transmitting messages using the MELSEC or OMRON protocol, specify MEMOBUS
protocol (=1). Protocol is converted by the communications device (217IF or 218IF).
• MEMOBUS: Setting = 1
• No-protocol 1: Setting = 2 (Data is sent or received in word units without using a proto-
col.)
• No-protocol 2: Setting = 3 (Data is sent or received in byte units without using a proto-
col.)
Note: For no-protocol transmissions, no response is received from the
sender.
CIR-NO (Line No.)
CIR-NO specifies the line number.
CH-NO (Channel No.)
CH-NO specifies the channel number of a communications unit. Only one channel number
can be set for the same line.
PARAM (Parameter List Leading Address)
PARAM specifies the leading address of the parameter list. For details on settings, refer to
A.1.3 Parameter Details.
Device
Line No.
215IF
1 to 8
217IF
1 to 24
218IF
1 to 8
Serial
1 or 2
Device
Channel No.
215IF
1 to 13
217IF
1
218IF
1 to 10
Serial
1
Applicable
Registers
Leading Address Examples
MW
DW
#W
MA00000, MA00100,
…
DA00000, DA00200,
…
#A00000, #A00300,
…