beautypg.com

2 setting switches, Rotary switches (sw1, sw2) – Yaskawa MP920 Communications Module User Manual

Page 67

background image

5 215IF Module

5.2.2 Setting Switches

5-6

The following table describes the operation of the LED indicators when a failure has
occurred.

Note: The number in parentheses ( ) after “Flashing” indicates the number

of flashes.

5.2.2

Setting Switches

„

Rotary Switches (SW1, SW2)

SW1 and SW2 set the address for 215IF Module communications. SW1 sets the first digit;
SW2 sets the second digit. Station addresses are numbered 1 to 64. These switches are effec-
tive only when the INIT switch is ON.

Failure

Meaning

LED Indicators

RUN

ERR

TX

RX

PROM Checksum
Error

A PROM checksum
error was detected dur-
ing online self-diagnosis.

Not lit

Flashing
(1)

Not lit

Not lit

Module Hardware
Error

A hardware error was
detected during online
self-diagnosis.

Not lit

Flashing
(2)

Not lit

Not lit

CPU Interface Error

A data transmission error
was detected between
Module and CPU during
online self-diagnosis.

Not lit

Flashing
(3)

Not lit

Not lit

Transmission Error

A normal transmission
error was detected.

Lit

Lit

Lit

Lit

Watchdog Timer
Error

A watchdog timer error
was detected.

Not lit

Flashing
(15)

Not lit

Not lit

Label

Name

Setting

Operation

ADRS
× 1

Address

× 1

1 to 10

The first digit of the station
address

ADRS
× 10

Address

×10

1 to 10

The second digit of the station
address

SW1

SW2

ADRS
X1

ADRS
X10