beautypg.com

Yaskawa MP920 Communications Module User Manual

Page 235

background image

Appendix A System Functions

A.1.3 Parameter Details

A-6

„

Remote Station Number (PARAM02)

„

Function Code (PARAM04)

Set the MEMOBUS function code to be sent.

Remote

Device

Remote

Station

Number

Meaning

CP-215

1 to 64

Message is sent to the designated station.

00FFH

Message is sent to all stations (broadcasting).

CP-216
(MECHA-
TROLINK)

1 to 30

Message is sent to the designated station. (Message can be sent only
from the master station.)

80H

Message is sent to the master station. (Message can be sent only
from salve stations.)

CP-217
(Serial)

1 to 254

Message is sent to the station with the specified device address.

0100H

“0100H” must be specified if the device address of the remote sta-
tion is 0.

CP-218

1 to 20

Message is sent to the station with the specified connection number.

Function

Code

Meaning

215IF, 218IF,

MECHA-

TROLINK*

217IF,

Serial*

00H

Not used.

No

No

01H

Coil status read

Yes

Yes

02H

Input relay status read

Yes

Yes

03H

Holding register read

Yes

Yes

04H

Input register read

Yes

Yes

05H

Single coil status change

Yes

Yes

06H

Single holding register write

Yes

Yes

07H

Not used.

No

No

08H

Loopback test

Yes

Yes

09H

Holding register read (extended)

Yes

No

0AH

Input register read (extended)

Yes

No

0BH

Holding register write (extended)

Yes

No

0CH

Not used.

No

No

0DH

Discontinuous holding register read
(extended)

Yes

No

0EH

Discontinuous holding register write
(extended)

Yes

No

0FH

Multiple coil status change

Yes

Yes

10H

Multiple holding register write

Yes

Yes

11H to 20H

Not used.

No

No

21H to 30H

Reserved by system.

No

No

31H

MELSEC fixed buffer communications

218IF only

No

32H

MELSEC random buffer read

218IF only

No