A.2 RECEIVE MESSAGE Function (MSG-RCV)

A-17

A

„

Remote Station Number (PARAM02)

PARAM02 outputs the station number of the sender.

For 218IF, specify the connection number of the destination.

„

Function Code (PARAM04)

Set the MEMOBUS function code to be sent.

* Yes: Can be output, No: Cannot be output

MB, MW, IB, and IW registers can be used as coils, holding registers, input relays, and input
registers during slave operation.

Function

Code

Meaning

215IF, 218IF,

MECHA-

TROLINK*

217IF,

Serial*

00H

Not used.

No

No

01H

Coil status read

Yes

Yes

02H

Input relay status read

Yes

Yes

03H

Holding register read

Yes

Yes

04H

Input register read

Yes

Yes

05H

Single coil status change

Yes

Yes

06H

Single holding register write

Yes

Yes

07H

Not used.

No

No

08H

Loopback test

Yes

Yes

09H

Holding register read (extended)

Yes

No

0AH

Input register read (extended)

Yes

No

0BH

Holding register write (extended)

Yes

No

0CH

Not used.

No

No

0DH

Discontinuous holding register read
(extended)

Yes

No

0EH

Discontinuous holding register write
(extended)

Yes

No

0FH

Multiple coil status change

Yes

Yes

10H

Multiple holding register write

Yes

Yes

11H to 20H

Not used.

No

No

21H to 30H

Reserved by system.

No

No

31H

MELSEC fixed buffer communications

218IF only

No

32H

MELSEC random buffer read

218IF only

No

33H

MELSEC random buffer write

218IF only

No

34H to 3FH

Reserved by system.

No

No

40H to 4FH

Reserved by system.

No

No

50H or later

Not used.

No

No