2 melsec communications, Melsec communications specifications – Yaskawa MP920 Communications Module User Manual
Page 138

6 217IF Module
6.6.2 MELSEC Communications
6-22
6.6.2
MELSEC Communications
MELSEC Communications Specifications
The following table shows the general specifications for MELSEC communications, and
which of these specifications are supported by the MP900.
000003
Other MEMOBUS Device
Coil
MP 900
Coil
MP 900
Coil
000002
000001
MB000002
MB000001
MB000000
MB001002
MB001001
MB001000
(Offset: Default is 0)
(Offset: 100)
MEMOBUS message
Table 6.8 MELSEC Communications Specifications
Item
General MELSEC Specifications
MELSEC Specifications Supported by
the MP900
Transmission Method
RS-232C: Half-duplex, full-duplex
RS-422: Half-duplex
RS-232C: Full-duplex
(Half-duplex for procedural)
RS-485: Half-duplex
Synchronization
Start-stop synchronization
Start-stop synchronization
Transmission Speed
300/600/1200/2400/4800/9600/19200 bps
1200/2400/4800/9600/19200 bps
Data Format
Data: 8 or 7 bits
Parity: Odd, even, none
Stop bits: 1 or 2 bits
Data: 8 or 7 bits
Parity: Odd, even, none
Stop bits: 1 or 2 bits
Error Detection
With or without checksum
With checksum
DTR/DSR (ER/DR)
Control
Yes/No (RS-232C only)
Both controls are
possible.
None
DC1/DC3, DC2/DC4
Control
Yes/No
Transmission Protocol
Special protocol
Only protocol type 1 is supported.
Type 1
(1:1, 1:N, N:N)
Type 2
Type 3
Type 4
No protocol (1:1, 1:N)
Full duplex (1:1)