beautypg.com

Connector pin layout – Yaskawa MP920 Communications Module User Manual

Page 121

background image

6.2 Part Names

6-5

6

The following table describes the operation of the LED indicators when a failure has
occurred.

Note: The number in parentheses ( ) under “Flashing” indicates the number

of flashes.

Connector Pin Layout

A 17LE-13090-27 (D2AC) D-sub 9-pin female connector (manufactured by Daiichi Elec-
tronic Industries Co., Ltd.) is used as the connector on the Module.

A 17JE-23090-02 (D8B) D-sub 9-pin male connector (manufactured by Daiichi Electronic
Industries Co., Ltd.) is used as the connector on the cable.

* The terminating resistance is put on the positive (+) side.

Failure

Meaning

Indicators

RUN

ERR

TX

RX

PROM Checksum
Error

A PROM checksum
error was detected dur-
ing online self-diagnosis.

Not lit

Flashing
(1)

Depends on the cir-
cumstances

SRAM Error in
Module

A hardware error was
detected during online
self-diagnosis.

Not lit

Flashing
(2)

Not lit

Not lit

CPU Interface Error

A data transmission error
was detected between
Module and CPU during
online self-diagnosis.

Not lit

Flashing
(3)

Not lit

Not lit

Transmission Error

A normal transmission
error was detected.

Lit

Lit

Depends on the cir-
cumstances

Watchdog Timer
Error

A watchdog timer error
was detected.

Not lit

Lit

Depends on the cir-
cumstances

Table 6.1 RS-232C Connectors (CN1/RS-232C, CN2/RS-232C)

Number

Signal

Name

Function

Number

Signal

Name

Function

1

FG

Protective ground

6

N.C.

Not connected

2

SD

Send data

7

SG

Signal ground (0 V)

3

RD

Receive data

8

N.C.

Not connected

4

RTS

Request to send

9

N.C.

Not connected

5

CS

Clear to send

Table 6.2 RS-422/485 Connectors (CN3/RS-422)

Number

Signal

Name

Function

Number

Signal

Name

Function

1

RX (-)

Receive data (-)

5

TRX (+)

*

2

RX (+)

Receive data (+)

6

TX (-)

Send data (-)

3

N.C

Not connected

7

TX (+)

Send data (+)

4

RXR (+)

*

8

SG

Signal ground