5 215IF Module

5.7.3 Specifications Common to All CP-215 Repeaters

5-44

System Configuration Using Star Connections

The following example shows a system configuration using star connections.

Fig. 5.12 System Configuration Using Star Connections

5.7.3

Specifications Common to All CP-215 Repeaters

„

Power Supply

ST#5

Up to foru Repeaters can be connected
between two stations.
In the start connection method,
Repeaters for branch lines are radially
connected from the electrical bus.

ST#4

ST#3

ST#2

ST#1

Repeater

Repeater

Repeater

Repeater

Repeater

Repeater

Repeater

Repeater

Repeater

Repeater

CP-215 electrical bus

1st

2nd

1st

2nd

Item

Specifications

Rated Input
Voltage

24-VDC Models

24 VDC

±20% (19.2 to 28.8 VDC)

100-VAC, 200-VAC,
100-VDC Models

100/115 VAC

±15% (85 to 132 VAC, 47 to 63 Hz)

100 VDC -10%, +40% (90 to 140 VDC)
200 VAC

±15% (170 to 230 VAC, 47 to 63 Hz)

Power
Consumption

24-VDC Models

5 W

100-VAC, 200-VAC,
100-VDC Models

10 W

Input Inrush
Current

24-VDC Models

5 A peak at 24 VDC

100-VAC, 200-VAC,
100-VDC Models

15 A peak at 100 VDC
15 A peak at 100 VAC
30 A peak at 200 VAC

Overcurrent
Protection

24-VDC Models

With built-in 1-A fuse

100-VAC, 200-VAC,
100-VDC Models

With built-in 2-A fuse

Holding Time

10 ms or less