6.6 217IF Communications Protocols

6-27

6

6.6.3

OMRON Communications

„

OMRON Communications Specifications

The following table shows the general specifications for OMRON communications, and

which of these specifications are supported by the 217IF Module.

Table 6.12 OMRON Communications Specifications

General OMRON Specifications

OMRON Specifications

Supported by the 217IF

Transmission
Method

RS-232C

RS-232C

Synchronization

Start-stop synchronization

Start-stop synchronization

Transmission
Speed

300/600/1200/2400/4800/9600 bps

1200/2400/4800/9600/19200 bps

Data Format

Data: 7-bit ASCII

8-bit JIS

Parity: Odd, even, none
Stop bits: 1 or 2 bits

Data: 7-bit ASCII

8-bit JIS

Parity: Odd, even, none
Stop bits: 1 or 2 bits

Error Detection

Frame check sequence (FCS)

Frame check sequence (FCS)

RTS/CTS Control Yes/No

Yes

Communications
Protocol

Host Link

Supported

Uploading or downloading of user
memory

Not supported

No protocol (ASCII I/O mode)

No protocol