beautypg.com

Yaskawa MP920 Communications Module User Manual

Page 245

background image

Appendix A System Functions

A.2.3 Parameter Details

A-16

2. COMMAND

3. RESULT

4. PARAMETER

PARAMETER indicates one of the error codes shown in Table A.2. when RESULT is
set to 4 (FMT_NG). Otherwise, it indicates the address of the remote station.

5. REQUEST

1 = Request

0 = Acceptance completion report

Code

Symbol

Meaning

1

U_SEND

General-purpose message sent.

2

U_REC

General-purpose message received.

3

ABORT

Aborted.

8

M_SEND

MEMOBUS command sent: Processing completed upon
receiving response.

9

M_REC

MEMOBUS command received: Followed by the sending
response.

C

MR_SEND

MEMOBUS response sent.

Code

Symbol

Meaning

1

SEND_OK

Sending has been completed normally.

2

REC_OK

Receiving has been completed normally.

3

ABORT_OK

Abort completed.

4

FMT_NG

Parameter format error

5

SEQ_NG, or INIT_NG Command sequence error:

The token has not been received yet.
The communications system has not been connected.

6

RESET_NG, or
O_RING_NG

Reset state:
Out-of-ring. The token was not be received even after
the token monitor time had elapsed.

7

REC_NG

Data receive error (error detected by a lower-level pro-
gram)

Table A.2 Error Codes

Code

Error

00

No errors.

01

Station address outside the allowable range

02

MEMOBUS response receiving time error

03

Retry count setting error

04

Cyclic area setting error

05

Message signal CPU number error

06

Message signal register number error

07

Message signal word count error