beautypg.com

D.1.2 in-panel cables – Yaskawa MP920 Communications Module User Manual

Page 304

background image

Appendix D Wiring Communications

D.1.2 In-panel Cables

D-12

D.1.2 In-panel Cables

The following table shows the in-panel cables used for communications.

Always use the specified cables. Otherwise, the communications system will fail to provide
its full performance.

When bending a communications cable, be sure that the bending radius is at least 10 times
the finished outer diameter of the cable.

Table D.2 Cable Bending Radius

Communications

System

Cable Type

Finished

Outer

Diameter

dl (mm)

Permissible

Bending

Radius

10 dl (mm)

Applicable Duct

215IF,
217IF
RS-485

Twisted-pair cable:
YS-IPEV-SB, 1P

× 0.3 mm,

manufactured by Fujikura Cor-
poration

5.6

56 min.

Low-voltage
duct

Twisted-pair cable:
YS-IPEV-SB, 3P

× 0.3 mm,

manufactured by Fujikura Cor-
poration

7.2

72 min.

Low-voltage
duct

217IF RS-232C

Low-voltage
duct

CP-215
Repeater

Coaxial cable:
3C-2V, manufactured by
Fujikura Corporation

5.6

56 min.

Special-purpose
duct

Coaxial cable:
3C-2V (Cu, Fe) ZV, manufac-
tured by Fujikura Corporation

8.6

86 min.

Low-voltage
duct

218IF

Transceiver cable:
DAISET-1581B, manufactured
by Mitsubishi Cable Industries,
LTD.

9.2

100 min.

Low-voltage
duct