D.5.2 217if transmission line components, Terminating resistors, In-panel cables with connectors – Yaskawa MP920 Communications Module User Manual
Page 318

Appendix D Wiring Communications
D.5.2 217IF Transmission Line Components
D-26
Terminating Resistors
Note: Use junction terminal blocks to install terminating resistors.
In-panel Cables with Connectors
D.5.2 217IF Transmission Line Components
217IF RS-485 Transmission Line Components
Cables
* 1. Refer to the Manufacturing Specifications No. II-95J6015.
* 2. Refer to the Manufacturing Specifications No. II-95J6015.
* 3. Pas1 refers to cable signal dB loss at 1 MHz. Z1 refers to cable charac-
teristic impedance at 1 MHz.
Note: Specify the desired model and cable length (in 500-m units) when
ordering.
Name
Model
Electrical
Product Code
Specifications
Usage
Manufacturer
Terminating
Resistor
ERO-
SICKF75R0
R002849
75
Ω ±1%, 1/2 W,
100 PPm
/°C
Mounted at both ends of
transmission line.
Two resistors required
for each transmission
line.
YASKAWA
ELECTRIC
CORPORA-
TION
Name
Model
Electrical
Product Code
Specifications
Usage
Manufacturer
JC215-02
Dedicated
Cable
−
87215-9900
Twisted-pair cable with
MR-8LF(G) and D-sub
9-pin connectors at
both ends.
Cable length: 3 m
For connection between
ACGC4000, MPE720
Programming Device,
and JC215-02
YASKAWA
ELECTRIC
CORPORA-
TION
Name
Model
Electrical
Product Code
Specifications
*3
Usage
Manufacturer
Twisted-pair
Cable
YS-IPEV-SB
*1,
1P
× 0.3 mm
2
−
Pas1: 25 dB/km
Z1: 78
Ω
For in-panel low-voltage
ducts
Fujikura Corpo-
ration
YS-IPEV-SB
*1
,
3P
× 0.3 mm
2
−
Pas1: 28 dB/km
Z1: 78
Ω
For in-panel low-voltage
ducts
Fujikura Corpo-
ration
YS-IPEV-S
(Cu)
*2
,
1P
× 1.25 mm
2
−
Pas1: 12 dB/km
Z1: 78
Ω
For panel-to-panel low-
voltage ducts
Fujikura Corpo-
ration