System Examples
SMA
Technologie AG
Page 98
SI3324/4248-14:SE2406
Installation Guide
The following parameters must be set:
No.
Parameter
Parameter value/unit
Parameter description
23-2
BatType
(see section 11.4)
refer to the data sheet
provided by the battery
manufacturer
The type of battery used in the system. To be
set when first commissioning the system (see
section 8.2 "Initialization" (Page 66)).
23-3
AmpHoursBat
(see section 11.4)
refer to the data sheet
provided by the battery
manufacturer
Battery capacity. To be set when first
commissioning the system (see section 8.2
"Initialization" (Page 66)).
23-4
AmpdcBatMax
(see section 11.4)
refer to the data sheet
provided by the battery
manufacturer
Max. battery charging current. To be set
when first commissioning the system (see
section 8.2 "Initialization" (Page 66)).
24-2
AmpacGenMax
0.85 * max. grid current
fuse
Max. generator output current (see section
8.5.2 "Setting the Output Current Limit"
(Page 77)).
24-8
GridConnected
(Stby)*
GridCharge (without
Sunny Boy inverter);
GridFeedPV (with Sunny
Boy inverter)
Operating mode of the Sunny Island 3324/
4248 when connected to the public grid (see
section 8.4 "Operating with the Public Grid"
(Page 72)).
40-2
Autostart
On
The Sunny Island 3324/4248 can restart
automatically.
40-6
LoadShedding
Auto
Automatic control of the load shedding relay
by the Sunny Island 3324/4248
40-8
SunnyBoys
Yes
Set this parameter to Yes when Sunny Boy
inverters are connected to the system.
*
* depending on national requirements
MSD: see 21 "Glossary" (Page 153)