Electrical Connection

SMA

Technologie AG

Page 42

SI3324/4248-14:SE2406

Installation Guide

4.

Install the three PE, N and L AC output conductors, one after the other. Insert
the appropriate conductor into the appropriate PE, N or L "AC output"
connection terminal and tighten the terminal screw firmly (torque 2.0 Nm to 4.0
Nm).

5.

Once all three connections have been made, tighten the metric-thread cable
screw connections firmly.

5.3.3 AC Input

The output of the generator/public grid is connected to the AC input of the Sunny
Island 3324/4248. Wire the AC input in the following sequence:

1.

Install an M25 metric-thread cable screw connection (included in delivery) in the
"AC input" cable feed-through (see figure Page 31).

-

Remove the dummy plug covering the cable feed-through.

-

Insert the metric-thread cable screw connection into the opening in the
housing.

-

Screw the counter-nut onto the cable screw connection thread inside the
housing.

Step 4.

Steps
1. + 3., 5.