5.3.2 AC Output

The stand-alone grid sub-distribution (e.g. loads, PV generator (Sunny Boy), wind
turbine (Windy-Boy)) is connected to the AC output of the Sunny Island 3324/4248.
If you wish to provide separate protection for an individual load circuit, then use a
maximum 16 A, B-type circuit breaker. In the case of a short circuit, the Sunny Island
3324/4248 can still trigger these types of automatic breakers:

1.

Install an M25 metric-thread cable screw connection (included in delivery) in the
"AC output" cable feed-through (see figure Page 31).

-

Remove the dummy plug covering the cable feed-through.

-

Insert the metric-thread cable screw connection into the opening in the
housing.

-

Screw the counter-nut onto the cable screw connection thread inside the
housing.

2.

Remove the protective insulation from each of the three conductors and fit a
suitable cable end sleeve to the exposed ends of each conductor.

3.

Feed the three-conductor cable through the metric-thread cable screw
connection into the housing of the Sunny Island 3324/4248.

Steps
1. + 3., 5.

Step 4.