SMA SI 3324 Installation User Manual
Page 139

SMA
Technologie AG
Menu Structure and Parameter Lists
Installation Guide
SI3324/4248-14:SE2406
Page 139
24-10
Transition
(B)
Ramp
Fast
Fast
Manner in which the Sunny Island 3324/
4248 switches from charging to inverter
operation if a grid or generator fault is
detected.
If problems occur when operating with
Sunny Boys, then select the "Ramp" option
here.
24-11
PGenRevers
(B)
0 to 1000 W
300
Maximum permissible generator reverse
power
24-12
PGenActiv
(B)
ON
OFF
OFF
Activation of the load-dependent
generator request (parameters 24-13 to
24-16 are activated)
24-13
PGenTAve
(B)
1 to 60 min
5
Average time after which the generator is
switched on or off (depending on "24-15
PGenOn" and the Sunny Island 3324/
4248 output power, see "11-4
PacInverter")
24-14
PGenTRun
(B)
1 to 60 min
10
Minimum generator run time
(independent of the Sunny Island 3324/
4248 output power, see "11-4
PacInverter"), after it has been switched
on as a result of a load-dependent
generator request. Once the minimum run
time has expired, the generator is again
switched according to the value of
parameter "24-13 PGenTAve".
24-15
PGenOn
(B)
1000 to 6000 W
3500
Output power at which the generator is
connected (connection time depends on
the "24-13 PGenTAve" parameter)
24-16
PGenOff
(B)
1 to 99 %
80
Output power "11-4 PacInverter" relative
to "24-15 PGenOn" at which the
generator is switched off (the average
value of output power in percent
according to the "24-14 PGenTRun"
parameter)
No.
Name
Range/
unit
Default
Description