10.2.1 Generators with Manual Start
A generator without an autostart feature must be started manually, i.e. by hand (see
section 8.5.3 "Generator Request" (Page 77)). A light can be connected to the
system to inform the user that the batteries have reached a critical state (see "12-4
BatState" parameter and section 11.3 "Deep Discharge Protection/Battery State"
(Page 105)) and must be charged. The following figure shows the wiring between
the generator and the Sunny Island 3324/4248:
The following parameters must be set:
The following subsections (10.2.1 to 10.2.4) show you a range of possible
ways how the generator connected to your system can be started.
No.
Parameter
Parameter value/unit
Parameter description
23-2
BatType
(see section 11.4)
refer to the data sheet
provided by the battery
manufacturer
The type of battery used in the system. To be
set when first commissioning the system (see
section 8.2 "Initialization" (Page 66)).
23-3
AmpHoursBat
(see section 11.4)
refer to the data sheet
provided by the battery
manufacturer
Battery capacity. To be set when first
commissioning the system (see section 8.2
"Initialization" (Page 66)).
23-4
AmpdcBatMax
(see section 11.4)
refer to the data sheet
provided by the battery
manufacturer
Max. battery charging current. To be set
when first commissioning the system (see
section 8.2 "Initialization" (Page 66)).
24-2
AmpacGenMax
0.85 * nominal generator
current (see generator
datasheet)
Max. generator output current (see section
8.5.2 "Setting the Output Current Limit"
(Page 77)).
40-2
Autostart
On
The Sunny Island 3324/4248 can restart
automatically.
40-6
LoadShedding
Auto
Automatic control of the load shedding relay
by the Sunny Island 3324/4248