2 generator start with a single contact (2-wire) – SMA SI 3324 Installation User Manual
Page 92

System Examples
SMA
Technologie AG
Page 92
SI3324/4248-14:SE2406
Installation Guide
Other parameters can also be changed for this system. You will find a list of these
parameters in section 17.2.2 "Adjustable System Parameters" (Page 134).
10.2.2 Generator Start with a Single Contact (2-Wire)
An autostart generator requiring a single contact (see section "2. "Direct" Setting"
(Page 76)) is directly connected to the Sunny Island 3324/4248. The wiring is shown
in the following figure:
The following parameters must be set:
40-8
SunnyBoys
Yes
Set this parameter only to Yes when Sunny
Boy inverters are connected to the system.
Load shedding is an important feature for protecting batteries from quick
aging caused by deep discharge. This is only activated when, over a longer
period of time, more energy is consumed than is generated, or when the
generator does not start (lack of fuel, generator fault).
No.
Parameter
Parameter value/unit
Parameter description
23-2
BatType
(see section 11.4)
refer to the data sheet
provided by the battery
manufacturer
The type of battery used in the system. To be
set when first commissioning the system (see
section 8.2 "Initialization" (Page 66)).
23-3
AmpHoursBat
(see section 11.4)
refer to the data sheet
provided by the battery
manufacturer
Battery capacity. To be set when first
commissioning the system (see section 8.2
"Initialization" (Page 66)).
23-4
AmpdcBatMax
(see section 11.4)
refer to the data sheet
provided by the battery
manufacturer
Max. battery charging current. To be set
when first commissioning the system (see
section 8.2 "Initialization" (Page 66)).
No.
Parameter
Parameter value/unit
Parameter description