SI3324/4248-14:SE2406

Installation Guide

Other parameters can also be changed for this system. You will find a list of these
parameters in section 17.2.2 "Adjustable System Parameters" (Page 134).

10.2.2 Generator Start with a Single Contact (2-Wire)

An autostart generator requiring a single contact (see section "2. "Direct" Setting"
(Page 76)
) is directly connected to the Sunny Island 3324/4248. The wiring is shown
in the following figure:

The following parameters must be set:

40-8

SunnyBoys

Yes

Set this parameter only to Yes when Sunny
Boy inverters are connected to the system.

Load shedding is an important feature for protecting batteries from quick
aging caused by deep discharge. This is only activated when, over a longer
period of time, more energy is consumed than is generated, or when the
generator does not start (lack of fuel, generator fault).

No.

Parameter

Parameter value/unit

Parameter description

23-2

BatType
(see section 11.4)

refer to the data sheet
provided by the battery
manufacturer

The type of battery used in the system. To be
set when first commissioning the system (see
section 8.2 "Initialization" (Page 66)).

23-3

AmpHoursBat
(see section 11.4)

refer to the data sheet
provided by the battery
manufacturer

Battery capacity. To be set when first
commissioning the system (see section 8.2
"Initialization" (Page 66))
.

23-4

AmpdcBatMax
(see section 11.4)

refer to the data sheet
provided by the battery
manufacturer

Max. battery charging current. To be set
when first commissioning the system (see
section 8.2 "Initialization" (Page 66)).

No.

Parameter

Parameter value/unit

Parameter description