Connecting Sunny Boy Inverters

Installation Guide

SI3324/4248-14:SE2406

Page 119

This completes the stand-alone grid parameter settings for the Sunny Boy.

4.

If Sunny Boy inverters are connected to a communications bus, then the "40-3
BaudRate" parameter of the Sunny Island 3324/4248 must be set to "1200".

5.

In the Sunny Island 3324/4248, the power adjustment via frequency - FSPC
(Frequency Shift Power Control) is activated using the "40-8 SunnyBoys"
parameter. Check that the parameter is set to "YES".

2

Uac-Min
Vac.Min (UL version)

V

180
107 (UL version)

3

Uac-Max
Vac.Max (UL version)

V

260
130 (UL version)

4

Fac-delta-

Hz

- 4.5 (starting from base frequency f

0

)

5

Fac-max+

Hz

+ 4.5 (starting from base frequency f

0

)

6

dFac-Max

Hz/s

4

7

Fac-start delta

Hz

1 (starting from base frequency f

0

)

8

Fac-Limit delta

Hz

2 (starting from base frequency f

0

)

No
.

Parameter

Unit Value