This completes the stand-alone grid parameter settings for the Sunny Boy.
4.
If Sunny Boy inverters are connected to a communications bus, then the "40-3
BaudRate" parameter of the Sunny Island 3324/4248 must be set to "1200".
5.
In the Sunny Island 3324/4248, the power adjustment via frequency - FSPC
(Frequency Shift Power Control) is activated using the "40-8 SunnyBoys"
parameter. Check that the parameter is set to "YES".
2
Uac-Min
Vac.Min (UL version)
V
180
107 (UL version)
3
Uac-Max
Vac.Max (UL version)
V
260
130 (UL version)
4
Fac-delta-
Hz
- 4.5 (starting from base frequency f
0
)
5
Fac-max+
Hz
+ 4.5 (starting from base frequency f
0
)
6
dFac-Max
Hz/s
4
7
Fac-start delta
Hz
1 (starting from base frequency f
0
)
8
Fac-Limit delta
Hz
2 (starting from base frequency f
0
)
No
.
Parameter
Unit Value