5.4.4 Generator Start with a Single Contact

The Sunny Island 3324/4248 can automatically start generators that can be started/
stopped using a single contact. This is done by the generator control relay
(GenRequest-Relay) integrated into the Sunny Island 3324/4248. The autostart
(single contact start) generator is directly connected to the "G_Req“ connection
terminals of the Sunny Island 3324/4248. Further information on parameter settings
and other methods of starting generators can be found in sections 8.5 "Operation
with a Generator" (Page 74)
and 10.2 "PV Stand-alone System with Generator"
(Page 90)
.

1.

Install an M20 metric-thread cable screw connection (included in delivery) in
one of the "Additional connections" cable feed-throughs (see figure Page 31).

-

Remove the dummy plug covering the chosen cable feed-through in the
housing.

-

Insert the cable screw connection thread into the opening in the housing.

-

Screw the appropriate M20 counter-nut onto the cable screw connection
thread inside the housing.

2.

Remove the protective insulation from the conductors and fit a suitable cable
end sleeve to the exposed ends of each conductor.

3

2

7

5

Shield

CA
N

_

L

C_GND

CA
N

_

H

FA
N

+

TB
A

T2

FAN-

TB
A

T1

S_IN-

S_OUT

-

S_IN+

S_OUT+

SHIELD

G_R

U

N-

SHIELD

G_R

U

N+

LO

AD_S

G_REQ

LO

AD_S

G_REQ