beautypg.com

SMA SI 3324 Installation User Manual

Page 73

background image

SMA

Technologie AG

Commissioning

Installation Guide

SI3324/4248-14:SE2406

Page 73

"GridFeedPV" Setting

Select the "GridFeedPV" setting when you operate the Sunny Island 3324/4248 in
parallel to a public grid and want to draw electrical energy from this grid and also
feed electrical energy produced in the stand-alone grid (e. g. from a PV generator
with a Sunny Boy) back into the public grid.
In this case, instead of the limits that can be defined using parameters 24-4 to 24-7,
the following predefined limits apply:

• Frequency: 49.8 Hz to 50.2 Hz
• Voltage: 190.0 V to 250.0 V

When using the "GridFeedPV" setting, set the "24-1 GenControl" parameter to
"Manual" and "24-3 GenOperation" parameter to "Auto".

The installer password is required in order to set parameters "24-4 to 24-16"
(see section 8.3 "Password Entry" (Page 69)
).

This manual is related to the following products: