Menu Structure and Parameter Lists
Installation Guide
SI3324/4248-14:SE2406
Page 135
23-5
NewBattery
(see section 11.4)
(Stby)
---
Reset
---
Reset the battery data stored in the
inverter. This parameter can only be set
when the inverter is in standby mode (see
section 9.3 "Switching Off" (Page 85)).
This parameter should only be set when
the batteries have been replaced. The
selection of "Reset" causes the Sunny
Island 3324/4248 to restart. This is
intentional.
23-6
TabsorbBoost
(B)
1 to 600 min
60
(VRLA),
45
(FLA)
Absorption period for boost charging
23-7
VchargeBoost
(B)
SI4248
44 to 62.4 VDC
56,8
(VRLA),
60
(FLA)
Desired voltage for boost charging
SI3324
27 to 31.2 VDC
28,8
(VRLA),
30
(FLA)
23-8
TabsorbEqual
(B)
1 to 1200 min
360
Absorption period for equalization
charge
23-9
VchargeEqual
(B)
SI4248
44 to 62.4 VDC
56,8
(VRLA),
60
(FLA)
Desired voltage for equalization charge
SI3324
27 to 31.2 VDC
28,8
(VRLA),
30
(FLA)
23-10
TabsorbFull
(B)
1 to 1200 min
180
(VRLA)
180
(FLA)
Absorption period for full charge
23-11
VchargeFull
(B)
SI4248
44 to 62.4 VDC
56,8
(VRLA),
60
(FLA)
Desired voltage for full charge
SI3324
27 to 31.2 VDC
28,8
(VRLA),
30
(FLA)
23-12
VchargeFloat
(B)
SI4248
44 to 62.4 VDC
54
(VRLA
and
FLA)
Desired voltage for float charge
SI3324
27 to 31.2 VDC
27
(VRLA
and
FLA)
No.
Name
Range/
unit
Default
Description