Menu Structure and Parameter Lists

Installation Guide

SI3324/4248-14:SE2406

Page 135

23-5

NewBattery
(see section 11.4)
(Stby)

---
Reset

---

Reset the battery data stored in the
inverter. This parameter can only be set
when the inverter is in standby mode (see
section 9.3 "Switching Off" (Page 85)).
This parameter should only be set when
the batteries have been replaced. The
selection of "Reset" causes the Sunny
Island 3324/4248 to restart. This is
intentional.

23-6

TabsorbBoost
(B)

1 to 600 min

60
(VRLA),
45
(FLA)

Absorption period for boost charging

23-7

VchargeBoost
(B)

SI4248
44 to 62.4 VDC

56,8
(VRLA),
60
(FLA)

Desired voltage for boost charging

SI3324
27 to 31.2 VDC

28,8
(VRLA),
30
(FLA)

23-8

TabsorbEqual
(B)

1 to 1200 min

360

Absorption period for equalization
charge

23-9

VchargeEqual
(B)

SI4248
44 to 62.4 VDC

56,8
(VRLA),
60
(FLA)

Desired voltage for equalization charge

SI3324
27 to 31.2 VDC

28,8
(VRLA),
30
(FLA)

23-10

TabsorbFull
(B)

1 to 1200 min

180
(VRLA)
180
(FLA)

Absorption period for full charge

23-11

VchargeFull
(B)

SI4248
44 to 62.4 VDC

56,8
(VRLA),
60
(FLA)

Desired voltage for full charge

SI3324
27 to 31.2 VDC

28,8
(VRLA),
30
(FLA)

23-12

VchargeFloat
(B)

SI4248
44 to 62.4 VDC

54
(VRLA
and
FLA)

Desired voltage for float charge

SI3324
27 to 31.2 VDC

27
(VRLA
and
FLA)

No.

Name

Range/
unit

Default

Description