4 exchanging the batteries, Exchanging the batteries – SMA SI 3324 Installation User Manual

Page 109

background image

SMA

Technologie AG

Battery Management

Installation Guide

SI3324/4248-14:SE2406

Page 109

The height of the three characteristic curves can be easily set using the parameters
"24-15 SocLim1", "24-16 SocLim2" and "24-17 SocLim3
". The charge level values set
here are automatically converted into characteristic curves.

The conversion is done using the following formula:

V

0

= 1.96 + 0.16 * SocLim

V

0

: Single cell open-circuit voltage (battery current = 0)

Since different types of battery also have slightly different current-voltage
characteristic curves, the state of charge (SOC) values set here may differ by up to
10 % from a state of charge (SOC) measured using ampere-hour balancing.

To achieve a sensible assignment of the state of charge (SOC) limits, the Sunny Island
3324/4248 firmware assigns your entered values in the following manner:

• Highest value = SocLim1
• Lowest value = SocLim3
• Any other value = SocLim2

11.4 Exchanging the Batteries

If you wish to exchange your batteries with new batteries, then the parameters

• "23-2 BatType"
• "23-3 AmpHoursBat"
• "23-4 AmpdcBatMax"
• "23-5 NewBattery"

must be reset to new values, with the inverter in standby mode. Proceed as follows:

1.

Set parameter 23-5 to "Reset"

2.

The Sunny Island 3324/4248 restarts

3.

The message "To init system press "
is displayed.

4.

Press .

If you enter 30 % for SocLim2 and 50 % for SocLim3, the Sunny Island 3324/
4248 firmware automatically corrects this and exchanges the values.