Battery meters generator meters – SMA SI 3324 Installation User Manual
Page 133

SMA
Technologie AG
Menu Structure and Parameter Lists
Installation Guide
SI3324/4248-14:SE2406
Page 133
Battery Meters
Generator Meters
No.
Name
Range/unit
Default
Description
12-1
BatVoltage
0 to 80 VDC
N/A
Battery voltage
12-2
BatCurrent
-200 to +200 ADC
N/A
Battery current
12-3
BatTemp
-40 to +200°C
N/A
Battery temperature
12-4
BatState
Normal Warning
Low
Critical
N/A
Battery state
12-5
BatChargeMode
Boost
Full
Float
Equalize
N/A
Battery charging process
12-6
TabsorbLeft
0 to max min
N/A
An absorption period is assigned to every
charging process. The Sunny Island 3324/
4248 must keep the generator running
during this time, even when this is only
partially loaded. The value of
"TabsorbLeft" shows the time remaining for
the absorption phase.
12-7
BatChargeVolt
SI 4248
44 to 62.4 VDC
Desired value of the battery charging
voltage
SI 3324
27 to 31.2 VDC
No.
Name
Range/
unit
Default
Description
13-1
VacGenerator
0 to 260 VAC
N/A
Inverter input voltage
(AC input)
13-2
AmpacGenerat
-60 to +60 AAC
N/A
Inverter input current
(AC input)
13-3
FacGenerator
0 to 70 Hz
N/A
Inverter input frequency
(AC input)
13-4
PacGenerator
-20 to +20 kWAC
N/A
Inverter input power
(AC input)