beautypg.com

Battery meters generator meters – SMA SI 3324 Installation User Manual

Page 133

background image

SMA

Technologie AG

Menu Structure and Parameter Lists

Installation Guide

SI3324/4248-14:SE2406

Page 133

Battery Meters

Generator Meters

No.

Name

Range/unit

Default

Description

12-1

BatVoltage

0 to 80 VDC

N/A

Battery voltage

12-2

BatCurrent

-200 to +200 ADC

N/A

Battery current

12-3

BatTemp

-40 to +200°C

N/A

Battery temperature

12-4

BatState

Normal Warning
Low
Critical

N/A

Battery state

12-5

BatChargeMode

Boost
Full
Float
Equalize

N/A

Battery charging process

12-6

TabsorbLeft

0 to max min

N/A

An absorption period is assigned to every
charging process. The Sunny Island 3324/
4248 must keep the generator running
during this time, even when this is only
partially loaded. The value of
"TabsorbLeft" shows the time remaining for
the absorption phase.

12-7

BatChargeVolt

SI 4248
44 to 62.4 VDC

Desired value of the battery charging
voltage

SI 3324
27 to 31.2 VDC

No.

Name

Range/
unit

Default

Description

13-1

VacGenerator

0 to 260 VAC

N/A

Inverter input voltage
(AC input)

13-2

AmpacGenerat

-60 to +60 AAC

N/A

Inverter input current
(AC input)

13-3

FacGenerator

0 to 70 Hz

N/A

Inverter input frequency
(AC input)

13-4

PacGenerator

-20 to +20 kWAC

N/A

Inverter input power
(AC input)

This manual is related to the following products: