3 ac connection, 1 cable protection, Ac connection – SMA SI 3324 Installation User Manual
Page 40: Cable protection, 3 "ac connection" (s. 40)), 3 ac connection 5.3.1 cable protection

Electrical Connection
SMA
Technologie AG
Page 40
SI3324/4248-14:SE2406
Installation Guide
5.3
AC Connection
5.3.1 Cable Protection
A sub-distribution panel must be used to connect the Sunny Island 3324/4248 to the
AC loads, a generator or the existing public grid. The sub-distribution panel must be
equipped with appropriate circuit breakers. Be sure to observe all the applicable
regional standards and guidelines.
Typical color codings for the AC installation are:
• Phase conductor (L conductor): brown
• Neutral conductor (N): blue
• Protective ground conductor (PE): green/yellow stripes
The Sunny Island 3324/4248 may only be used in grids where the N conductor is
grounded.
The maximum permissible current that may flow through the AC input of the
Sunny Island 3324/4248 is 56 A.
The neutral conductor (N conductor) is looped through the Sunny Island 3324/
4248, i.e. the N connection terminals of AC output and AC input are connected
inside the inverter.