The cells with a grey background in the following tables show all menu items that can
only be changed after entering the installer password. Only parameters in the menu
branches "20-Settings" and "40-Operation" can be changed. The other values are
only displayed in the Sunny Island 3324/4248 display. Proceed carefully when
changing parameter settings, because incorrect settings can lead to undesireable
operation of the inverter.
17.2.1 Displayed Measurement Values
Inverter Meters
Take note of the original values of all parameters that you change.
The "40-4 ParameterSet" parameter allows all the current parameter settings
to be saved. This is especially useful if you wish to try out new settings. Once
the system is working optimally, i. e. the selected settings have proven
effective, then you can use the "40-4 ParameterSet“ to load or discard the
stored values in the Sunny Island 3324/4248 (see section 17.2.4 "Operation
(Operation)" (Page 141)).
No.
Name
Range/
unit
Default
Description
11-1
VacInverter
0 to 300 VAC
N/A
Inverter output voltage
11-2
AmpacInverter
-70 to +70 AAC
N/A
Inverter output current
11-3
FacInverter
0 to 70 Hz
N/A
Inverter frequency
11-4
PacInverter
-10,000 to
+10,000 W
N/A
Inverter AC output power
11-5
TrfTemp
— °C
N/A
Transformer temperature
11-6
HsTemp
— °C
N/A
Heat sink temperature