SI3324/4248-14:SE2406

Installation Guide

Generator Settings

23-13

TcycleFull
(B)

1 to 180 days

14

Number of days after which the next full
charge will occur (see also section 11.1
"Charge Control" (Page 102))

23-14

TcycleEqual
(B)

7 to 365 days

60

Number of days after which the next
equalization charge will occur (see also
section 11.1 "Charge Control"
(Page 102))

23-15

SOCLim1
(B)

0 to 100 %

40

Charge level at which the generator is
started (see section 11.3 "Deep Discharge
Protection/Battery State" (Page 105))

23-16

SOCLim2
(B)

0 to 100 %

30

Charge level at which load shedding will
occur (see section 11.3 "Deep Discharge
Protection/Battery State" (Page 105))

23-17

SOCLim3
(B)

0 to 100 %

20

Charge level at which the Sunny Island
3324/4248 switches off (see section 11.3
"Deep Discharge Protection/Battery
State" (Page 105))

23-18

TBatMax
(B)

0 to 55°C

45

Maximum battery temperature

No.

Name

Range/
unit

Default

Description

24-1

GenControl
(B)

Manual
Direct
GenMan

Manual

The generator start option to be used in
your system (see section 8.5.1 "Selection
of Generator Control Method"
(Page 75))
.
Manual: Manual start or no generator
connected
Direct: Generator start using the Sunny
Island 3324/4248 "GenRequest" control
relay
GenMan: Generator start using the
(optional) GenMan

24-2

AmpacGenMax
(B)

2 to 56 AAC

10

Max. generator current that the Sunny
Island 3324/4248 will demand from the
generator (see section 8.5.2 "Setting the
Output Current Limit" (Page 77))
.
Note: If the system load exceeds this
value, the Sunny Island 3324/4248 will
not switch to the generator, to avoid
overloading it. Ensure that a sensible
value is entered here!

No.

Name

Range/
unit

Default

Description