beautypg.com

SMA SI 3324 Installation User Manual

Page 137

background image

SMA

Technologie AG

Menu Structure and Parameter Lists

Installation Guide

SI3324/4248-14:SE2406

Page 137

24-3

GenOperation
(B)

Auto
Start
Stop
Run1h
Release

Auto

Auto: Automatic start of the generator is
activated.
Start: The generator is immediately
started (the display shows "S").
Remember to stop the generator again
when you no longer require it (by
selecting either "Stop" or "Auto").
Stop: The generator is immediately
stopped. Remember to set the generator
back to "Auto" if you want the Sunny
Island 3324/4248 to once more assume
control.
Run1h: The generator is immediately
started and will run for one hour (the
display shows "T"). After this, the Sunny
Island 3324/4248 returns to the
previously active mode.
Release: Interrupts the lockout time (20
min) for the generator after a
"ReversePower" fault has occurred.

24-4

VacGenMax
(B)

230 to 250 VAC

240

Maximum permissible generator voltage.
If the generator voltage is higher than this
limit, the Sunny Island 3324/4248 does
not connect to the generator. If the
generator voltage exceeds this limit while
being connected to the stand-alone grid,
then the Sunny Island 3324/4248
disconnects the generator from the stand-
alone grid.

Only valid when the "24-8
GridConnected" parameter is set to
"GridNone".

(250)

The value in brackets applies when the
"24-8 GridConnected" parameter is set to
"GridCharge" or "GridFeedPV". This
value cannot be changed and is not
displayed.

24-5

VacGenMin
(B)

172.5 to 230 VAC

200

Minimum permissible generator voltage.
If the generator voltage is lower than this
value, the Sunny Island 3324/4248 does
not connect to the generator. If the
generator voltage drops below this value
while being connected to the stand-alone
grid, then the Sunny Island 3324/4248
disconnects the generator from the stand-
alone grid.

Only valid when the "24-8
GridConnected" parameter is set to
"GridNone".

(190)

The value in brackets applies when the
"24-8 GridConnected" parameter is set to
"GridCharge" or "GridFeedPV". This
value cannot be changed and is not
displayed.

No.

Name

Range/
unit

Default

Description

This manual is related to the following products: