18.2 Troubleshooting FAQs

Here you will find answers to frequently asked questions (FAQs):

1.

The Sunny Island 3324/4248 does not switch to the running generator, even
though the generator control relay has closed (Gen_Request) (the "24-1
GenControl" parameter is set to "Direct", see Page 76).

-

Check the generator fuses.

TR-TempOV

Excessive transformer temperature:
The Sunny Island 3324/4248 has been
operated under overload conditions for
an extended period of time.
The ambient temperature is very high
while the Sunny Island 3324/4248 is
being operated with a heavy load.

The Sunny Island 3324/4248 can only
restart when the transformer has cooled
by a minimum of 5°C.
Place the Sunny Island 3324/4248 in
standby mode for a few minutes to allow
the fans to cool the inverter.
Switch off some of the connected loads in
the stand-alone grid to avoid immediately
overloading the Sunny Island 3324/4248
after a restart.
If the "40-2 Autostart" parameter is set to
"On", the Sunny Island 3324/4248
automatically starts once the transformer
temperature has sunk by 5°C.

VAC-High

Output

voltage

too

high

Check the value of the "22-1
VacNominal" parameter setting (see
section 17.2.2 "Adjustable System
Parameters" (Page 134))
.

VAC-Low

Output

voltage

too

low

Check the value of the "22-1
VacNominal" parameter setting (see
section 17.2.2 "Adjustable System
Parameters" (Page 134))
. For an
explanation, refer to point 7 of section
18.2 "Troubleshooting FAQs" (S. 145).

Short-circuit in the system

Check the system for a possible short-
circuit.

VBatHigh

Battery voltage too high:

Check the battery connections (see
section 5.2 "DC Connection" (Page 36)).

External charger with excessive
charging voltage

Check the external charger.

One or more defective batteries with
high internal resistance

Check the batteries.

VBatLow

Battery voltage too low:
wrong parameter setting

Check the value of the "23-1
VdcBatNominal" parameter setting (see
section 17.2.2 "Adjustable System
Parameters" (Page 134))
.

Deeply

discharged

batteries

Recharge the batteries as soon as
possible.

One or more defective batteries

Check the batteries.

Watchdog

Automatic

reset

If this fault frequently occurs please
contact the SMA hotline (see section 20
"Contact" (Page 151)
).

Fault display

Cause

Fault correction