SMA SI 3324 Installation User Manual
Page 96

System Examples
SMA
Technologie AG
Page 96
SI3324/4248-14:SE2406
Installation Guide
The following parameters must be set:
Other parameters can also be changed for this system. You will find a list of these
parameters in section 17.2.2 "Adjustable System Parameters" (Page 134).
No.
Parameter
Parameter value/unit
Parameter description
23-2
BatType
(see section 11.4)
refer to the data sheet
provided by the battery
manufacturer
The type of battery used in the system. To be
set when first commissioning the system (see
section 8.2 "Initialization" (Page 66)).
23-3
AmpHoursBat
(see section 11.4)
refer to the data sheet
provided by the battery
manufacturer
Battery capacity. To be set when first
commissioning the system (see section 8.2
"Initialization" (Page 66)).
23-4
AmpdcBatMax
(see section 11.4)
refer to the data sheet
provided by the battery
manufacturer
Max. battery charging current. To be set
when first commissioning the system (see
section 8.2 "Initialization" (Page 66)).
24-1
GenControl
GenMan
Generator type (see section 8.5.3
"Generator Request" (Page 77))
24-2
AmpacGenMax
0.85 * nominal generator
current (see generator
datasheet)
Max. generator output current (see section
8.5.2 "Setting the Output Current Limit"
(Page 77)).
40-2
Autostart
On
The Sunny Island 3324/4248 can restart
automatically.
40-6
LoadShedding
Auto
Automatic control of the load shedding relay
by the Sunny Island 3324/4248
40-8
SunnyBoys
Yes
Set this parameter to Yes when Sunny Boy
inverters are connected to the system.
Load shedding is an important feature for protecting batteries from quick
aging caused by deep discharge. This is only activated when, over a longer
period of time, more energy is consumed than is generated, or when the
generator does not start (lack of fuel, generator fault).