beautypg.com

18 troubleshooting/problem solving, 1 list of fault displays, Troubleshooting/problem solving – SMA SI 3324 Installation User Manual

Page 143: List of fault displays

background image

SMA

Technologie AG

Troubleshooting/Problem Solving

Installation Guide

SI3324/4248-14:SE2406

Page 143

18 Troubleshooting/Problem Solving

18.1 List of Fault Displays

The meaning of fault messages displayed by the Sunny Island 3324/4248 are
explained in the following table:

Fault display

Cause

Fault correction

CBT-Open

The battery temperature sensor is
missing or not correctly connected.

Connect the battery temperature sensor
(see section 5.4.2 "Battery Temperature
Sensor" (Page 46)
).

The battery temperature sensor cable is
defective.

Change the battery temperature sensor.
Warning: Do not shorten the battery
temperature sensor cables!

CBT-Short

Short-circuit in the battery temperature
sensor.

Change the battery temperature sensor.
Warning: Do not shorten the battery
temperature sensor cables!

The battery temperature sensor cable is
defective.

Change the battery temperature sensor.
Warning: Do not shorten the battery
temperature sensor cables!

ChargeLow

This fault occurs when the battery state
remains in the critical area for an
extended period of time ("Critical"), i.e.
the batteries have not been charged in
time (see section 11.3 "Deep Discharge
Protection/Battery State" (Page 105))
.
Possible causes:

The Sunny Island 3324/4248 can be
started to charge the batteries after the
fault has been confirmed.
Requirements:
The system has enough energy available
for charging the batteries from a
generator or the public grid.

The generator does not start when
requested by the Sunny Island 3324/
4248.

Check the generator fuses.

Check the fuel supply (diesel).

Energy consumption is higher than that
provided by the power generator (e.g.
PV generator).

Switch off the energy consumers/loads.

CHS-Open

Device fault

Please contact the SMA hotline (see
section 20 "Contact" (Page 151)).

CHS-Short

Device fault

Please contact the SMA hotline (see
section 20 "Contact" (Page 151)).

CTR-Open

Device fault

Please contact the SMA hotline (see
section 20 "Contact" (Page 151)).

CTR-Short

Device fault

Please contact the SMA hotline (see
section 20 "Contact" (Page 151)).

FailSet

Device fault

Please contact the SMA hotline (see
section 20 "Contact" (Page 151)).

HotACout

The Sunny Island 3324/4248 will not
start because voltage already exists on
the AC output terminals.

Check for installation faults at the AC
connections (see section 5.3 "AC
Connection" (Page 40))
.

Installation fault in the stand-alone grid.

Remove all voltages from the AC output of
the Sunny Island 3324/4248. Repeat the
start process.

This manual is related to the following products: