Installation Guide

12.4 Display Message

The following table describes the status of the generator voltage and generator
frequency, as they are shown in the display:

Display

Description

*

The generator voltage and frequency lie within the defined limits
(see Generator Settings: parameters 24-4 to 24-8, installer level).

?

The generator voltage and/or frequency lie outside the defined
limits (see Generator Settings: parameters 24-4 to 24-8, installer
level). The Sunny Island 3324/4248 will not connect the
generator to the stand-alone grid while this situation exists.

!

The maximum permissible generator reverse power ("24-11
PGenReverse" parameter, installer level) has been exceeded. The
Sunny Island 3324/4248 has removed the generator from the
stand-alone grid. The generator cannot be reconnected to the
stand-alone grid for a period of 20 minutes. This lockout can be
removed by setting the "24-3 GenOperation" parameter to
"Release".

[¿¿¿¿¿¿¿¿¿¿¿¿ ]

>Invert L oo E

Output power/charging power

Load shedding

relay status

Generator status

Request Type

Generator control

relay status

Fault display

Load status

Direction of energy

flow

Operating mode