12.2 Temperature-dependent Generator Request

Activation of load-dependent generator requests (see above - "24-12 PGenActiv"
parameter set to "ON") also switches on temperature-dependent generator requests.
The operating temperature of the Sunny Island 3324/4248 is used as the
measurement value.

When the Sunny Island 3324/4248 is operated under heavy loads for an extended
period of time, it may switch off to avoid damage through overheating. In this case,
a complete dropout of the stand-alone grid will occur and the loads will no longer be
supplied.

The "Temperature-dependent generator request" function prevents this grid dropout.
Before the Sunny Island 3324/4248 must switch off due to overheating, it can
request a generator start and switches the stand-alone grid to the generator. The
Sunny Island 3324/4248 can now charge the batteries, as long as the temperature
allows this. The generator provides the stand-alone grid and provides the loads with
electrical energy.

The minimum run time and the switch-off conditions for the generator in this menu
match the values for load-dependent generator requests (see section 12.1 "Load-
dependent Generator Request" (Page 111))
.

12.3 GenMan

Complex Generator Start: GenMan

The optional GenMan (SMA order number: SI GenMan) allows the Sunny Island
3324/4248 to control generators requiring more than a simple start/stop signal. You
can purchase the GenMan from your local dealer. More information on this SMA
product can be found in the GenMan operating manual.

.

The connection of a generator using GenMan and the Sunny Island 3324/4248 is
described in more detail in section 10 "System Examples" (Page 87).

e.g.

5 status LEDs

configuration

switch,

manual

activation

Signal 1

Signal 2

Signal 3

12 V DC supply voltage

12 V AC

control voltage

Starter battery

Transformer included in delivery GenMan

Request

Status