9 Sensor specifications

135

Cables for intrinsically safe installation:

− 10 m (33 ft) cable, part number PR-8230-010, connecting the Indicating transmit-

ter STR and the Isolator unit.
The maximum cable length is 100 m (330 ft).

− 10 m (33 ft) power cable, part number PR-8250-010, connecting the Indicating

transmitter STR and the Isolator unit, part number PR-8250-010. The maximum
length is 100 m (330 ft).

− The intrinsically safe cable between Isolator unit and sensor, part RP-8260-xxx,

where xxx is the cable length in meters. The maximum length is 200 m (660 ft).
For cable connections see Figures 9.38 and 9.40.

Note: Isolator/Barrier Unit can also use an optional external +24V DC power supply
instead of the +24V DC power supply from the transmitter. +24V DC is connected to
terminals 13 and 14. (If +24V DC is used, the PR-8250 power cable is not used at all.)

9.11.3 Isolator/barriers

Isolator unit wiring is explained below in Figure 9.40.

2

1

3

5

4

6

8

7

9

11

10

12

13

14

+ve

-ve

+ve

-ve

-vs

+vs

ISOLATOR UNIT

24VDC

Power cable
PR-8250-xxx

(max 100m)

(max 100m)

(max 200m)

Cable
PR-8230-xxx

1

2

Cable
PR-8260-xxx

Figure 9.40

Isolator unit wiring

Note: If the power to Isolator unit terminals is not correctly connected, +24V DC to
terminal 14 (+vs) and zero to terminal 13 (-vs), the transmitter STR will give the mes-
sage

No signal

. Also if terminals 11 and 12 are not correctly connected, sensor cable

connecting terminal 2 of the Indicating transmitter STR to the Isolator unit terminal
11 (-ve) and terminal 1 of the STR to Isolator unit terminal 12 (+ve) , the message

No

signal

will appear.