3 alarm relay, 1 air flow switch alarm, 2 anti-freeze alarm – EVCO EPK4BHQ1AH Installer manual User Manual

Page 97

background image

EVCO S.p.A.

c-pro 3

NODE kilo AHU | Application manual ver. 1.0

page 97 of 114

or disconnected

which the sensor is dependent

AL28

I/O configuration error

Auto

Shuts down all devices

-

AL29

RTC Alarm broken or discharged

A/M

Inhibits management of the

time zone

-

AL30

External air damper end run

A/M

Shuts down all devices

Configurable

A/M: Automatic or Manual alarm (set from parameter)

(*¹) To re-arm alarms connected to the hours of operation you need only reset the hours on the device to zero.

(*²) These alarms cause the unit to shutdown bringing it to the status OFF from alarm

7.2.1

Air flow switch alarm

The flow meter can be managed after the initial Start-up phase of the unit and after the Flow meter delay from reset

PA28: once this time elapses, if the contact indicates lack of flow, the alarm will be raised immediately.

During normal operation the flow sensor is continuously monitored: if the contact indicates lack of flow for a period

greater than that at parameter PA29 the alarm will be raised immediately.

The flow meter alarm is restored manually; activation requires the shutdown of the unit bringing it to the state of

Alarm OFF).

7.2.2

Anti-freeze alarm

The method used to enable the alarm is configurable with parameter PA35:

PA35=0:

alarm disabled

PA35=1:

alarm at digital input

7.3

Alarm relay

The program provides the possibility to manage a relay for a configurable alarm. For each type of alarm there is a

parameter that permits you to choose whether that particular alarm must be signalled on the alarm relay. Additional

alarms can be addressed at relay. Using the relative parameter (PH60) it is possible to define the polarity (NO, or NC)

of the digital output of the alarm.

Unit

ON

OFF

Flow

ON

ON

Alarm

PA28

PA29

P