Note: the outdoor air temperature sensor must also be enabled (PH40=1). When the control sensors are in error the

function is disabled.

6.17.4

Recovery device status

The heat recovery device may assume one of the following modes of operation:

1.

Disabled: the recuperation is not being managed. In this status in the user interface you will see the symbol

”.

2.

Off: the heat recovery device is off. In the user interface you will see written “ON” when in this state “OFF”.

3.

In defrosting mode: the heat recovery devices is off and defrosting is activated (only when heat recovery

device is at cross flow, PG13=1). In this state in the user interface you will see written (and flashing)

OFF_D”.

4.

Off for free-cooling/heating: the heat recovery device is off (because of a request for free-cooling/heating). In

this status in the user interface you will see written “OFF_F”.

5.

On: heat recovery device is on. In the user interface you will see written “ON” when in this state “ON”.

6.18

Heating/cooling pumps

A simple method for managing the two circulation pumps (for heating/cooling) is provided. In order to enable the

cooling pump you need to set parameter PG10 to 1. To enable the heating pump you will need to set parameter PG11

to 1 in the Configuration menu.

Based on the requirement you may choose between two controls by going to parameter PP01 (continuous control,

On/Off control).

6.18.1

Continuous control

The continuous control is dependent on the status of the central unit. The pumps will Start-up and shutdown each

time the machine starts up and shuts down. In order to set this control select PP01=0.

6.18.2

Control On/Off

The circulation pumps will activate when there is an actual heating/cooling request which exceeds a Start-up set

(PP02) and they shutdown when the same request falls below a certain shutdown set (PP03). In order to set this

control select PP01=1.

Pr01:

Set

Point

Heat

0 %

| T.Exhaust – T.Outdoor |

Pr02:

100%