2 mqtt, 3 modbus tcp/ip – EVCO EPK4BHQ1AH Installer manual User Manual
Page 100

EVCO S.p.A.
c-pro 3
NODE kilo AHU | Application manual ver. 1.0
page 100 of 114
8.2
MQTT
As default, the MQTT functionality is disabled.
To enable it it is necessary to gain access to hte menu Networks > (password -19) > Ethernet.
Scroll the items until “Enable MQTT”.
Set 1 to enable sending the dta to the defined Broker.
Scroll the voices until “MQTT broker IP”, then configure the desired broker IP.
As default the value is
176.58.125.240
This is the address of the EVCO server.
Scroll the voices until “MQTT port”.
This is the communication port with the broker. The default value is 1883.
Scroll the items until “MQTT time zone”.
This value is the time zone of the Country the device is installed.
The dafault is 1 (+1 h) which is the value for Italy.
Scroll the items until “MQTT time zone”.
This is the setting for the daylight saving time:
-
1 the running date is daylight saving time
-
0 the running date is not daylight saving time.
8.3
ModBus TCP/IP
The MODBUS TCP/IP service exports all the variables there are in the project list.
As standard setting, the access is on port 502 (standard setting for MODBUS use via TCP/IP).
It is possible to modify the port using the menu Networks > (password -19) > Ethernet.
Scroll the items until “Port MB Slave” and type the desired value.