15 humidification, 1 enabling humidifier (flow temperature operation), 2 humidifier on/off – EVCO EPK4BHQ1AH Installer manual User Manual

Page 82

background image

EVCO S.p.A.

c-pro 3

NODE kilo AHU | Application manual ver. 1.0

page 82 of 114

6.15

Humidification

To adjust the comfort of the room it is necessary to also consider the humidity in the air and to regulate it based on a

determined Set point desired percentage (PU01) and at a neutral zone (PU02). If the room humidity sensor is present

it is possible to command the humidifier using On/Off switch or by using the module.

Humidity management is enabled by activating the parameter PG06>0, in the configuration menu. The room air

humidity sensor is also activated (PH41=1), if the sensor is disabled or in error dehumidification management will be

inhibited.

6.15.1

Enabling humidifier (flow temperature operation)

In order to function correctly the humidifier requires a minimum value for air temperature, for which it identifies a Set

point (PU11) and relative hysteresis (PU12) on the flow temperature to enable/disable the humidifier. This function is

enabled by parameter PU10. In case PU10=0 (function disabled) the humidifier will Start-up/shutdown on the normal

Set point percentage (PU01).

With the flow sensor in error the function is inhibited and the humidifier will Start-up/shutdown on the Set point

percentage.

6.15.2

Humidifier On/Off

In order to utilize the On/Off control of the humidifier you must set parameter PG06 to 1.

Note: in order to utilize this function it is necessary to enable the room humidity sensor, setting parameter PH41 to 1.

When the sensor is in error the humidifier is shut off.

PU11: Set Point

OFF

T. Supply

PU12 Diff.

ON

PU01:

Set

OFF

PU03:

ON

NZ

PU02

Room Humidity

%