When the control ramp exceeds PP02 the pump will activate; when it falls below PP03 a timer will activate keeping the

pump active for a set period of time (parameter PP04). The timer resets if the ramp returns above PP02. The pump

will be shut down by using the shutdown command from the unit cancelling the active timer.

Note: in case where the primary control is on the fans (PG04=0), this control can be used only if the fan control is in

the modulating type.

6.18.3

Pump status

Both pumps may assume any of the following operating states:

7.

Disabled: the pump is not managed by the controller. In the user interface you will see the symbol “ - “ when

in this state.

8.

Off: the pump is off. In the user interface you will see written “ON” when in this state “OFF”.

9.

Waiting for shutdown: the pump is in the process of shutting down, and is in queue for scheduled protection.

In this status in the user interface you will see written (and flashing) “WOFF”.

10.

On: the pump is on. In the user interface you will see written “ON” when in this state.

11.

Alarm: the pump alarms are on. In the user interface you will see written “ALARM” when in this state.

6.18.4

Pump alarm inputs

Thermal pump alarm management is provided for both configured pumps.

Control ramp

PP02: Set % Pump

PP03: Set % Pump

Ramp %

Pump

ON

OFF