2 table of alarms – EVCO EPK4BHQ1AH Installer manual User Manual
Page 96

EVCO S.p.A.
c-pro 3
NODE kilo AHU | Application manual ver. 1.0
page 96 of 114
7.2
Table of Alarms
The following is a list of all the alarms managed by the application.
The order of presentation is the same as the
order of presentation for the active alarms.
All alarms can be viewed even when the machine is off.
Code
Description of the alarm
Rearm
Consequence
Delay
AL01
Thermal alarm fan (*²)
Or alarm inverter (flow)
Auto
Shuts down all devices
Fixed 2 sec.
AL02
Thermal alarm fan (*²)
Or alarm inverter (return)
Auto
Shuts down all devices
Fixed 2 sec.
AL03
Flow air flow switch (*²)
Manu
Shuts down all devices
Configurable
AL04
Return air flow switch (*²)
Manu
Shuts down all devices
Configurable
AL05
Thermal circulation heating pump
Auto
Stops the pump
Fixed 2 sec.
AL06
Thermal circulation cooling pump
Auto
Stops the pump
Fixed 2 sec.
AL07
Heating elements circuit breaker alarm
(*²)
Auto
Shuts down all devices
Fixed 2 sec.
AL08
Air filter pressure switch
A/M
Display
Configurable
AL09
Humidifier
A/M
Stops the humidifier
Configurable
AL10
General alarm
A/M
Shuts down all devices
Configurable
AL11
Anti-freeze
Auto
Shuts down fans and closes
the shutter
Forces heating coil to 100%
Forces cooling coil to 0%
Configurable
AL12
Heat recovery device alarm
Auto
Activates the heat recovery
device by-pass
Configurable
AL13
Fire/smoke Alarm (*²)
Auto
Shuts down all devices
-
AL14
Operating hours - flow fans
Manu*¹
Display
-
AL15
Operating hours - return fan
Manu*¹
Display
-
AL16
Operating hours - coil 1 pump
Manu*¹
Display
-
AL17
Operating hours - coil 2 pump
Manu*¹
Display
-
AL18
Room temperature probe/return broken
or disconnected
Auto
Inhibits the controls upon
which the sensor is dependent
Configurable
AL19
Discharge air temperature sensor broken
or disconnected
Auto
Inhibits the controls upon
which the sensor is dependent
Configurable
AL20
Outdoor air temperature sensor broken or
disconnected
Auto
Inhibits the controls upon
which the sensor is dependent
Configurable
AL21
Room humidity probe/return broken or
disconnected
Auto
Inhibits the controls upon
which the sensor is dependent
Configurable
AL22
Exhaust air temperature sensor broken or
disconnected
Auto
Inhibits the controls upon
which the sensor is dependent
Configurable
AL23
Channel
pressure
probe
broken
or
disconnected
Auto
Inhibits the controls upon
which the sensor is dependent
Configurable
AL24
Air quality probe broken or disconnected
Auto
Inhibits the controls upon
which the sensor is dependent
Configurable
AL25
Flow
humidity
sensor
broken
or
disconnected
Auto
Inhibits the controls upon
which the sensor is dependent
Configurable
AL26
Remote set point variator potentiometer
broken or disconnected
Auto
Inhibits the controls upon
which the sensor is dependent
Configurable
AL27
Dampers opening potentiometer broken
Auto
Inhibits the controls upon
Configurable