2 table of alarms – EVCO EPK4BHQ1AH Installer manual User Manual

Page 96

background image

EVCO S.p.A.

c-pro 3

NODE kilo AHU | Application manual ver. 1.0

page 96 of 114

7.2

Table of Alarms

The following is a list of all the alarms managed by the application.

The order of presentation is the same as the

order of presentation for the active alarms.

All alarms can be viewed even when the machine is off.

Code

Description of the alarm

Rearm

Consequence

Delay

AL01

Thermal alarm fan (*²)

Or alarm inverter (flow)

Auto

Shuts down all devices

Fixed 2 sec.

AL02

Thermal alarm fan (*²)

Or alarm inverter (return)

Auto

Shuts down all devices

Fixed 2 sec.

AL03

Flow air flow switch (*²)

Manu

Shuts down all devices

Configurable

AL04

Return air flow switch (*²)

Manu

Shuts down all devices

Configurable

AL05

Thermal circulation heating pump

Auto

Stops the pump

Fixed 2 sec.

AL06

Thermal circulation cooling pump

Auto

Stops the pump

Fixed 2 sec.

AL07

Heating elements circuit breaker alarm

(*²)

Auto

Shuts down all devices

Fixed 2 sec.

AL08

Air filter pressure switch

A/M

Display

Configurable

AL09

Humidifier

A/M

Stops the humidifier

Configurable

AL10

General alarm

A/M

Shuts down all devices

Configurable

AL11

Anti-freeze

Auto

Shuts down fans and closes

the shutter

Forces heating coil to 100%

Forces cooling coil to 0%

Configurable

AL12

Heat recovery device alarm

Auto

Activates the heat recovery

device by-pass

Configurable

AL13

Fire/smoke Alarm (*²)

Auto

Shuts down all devices

-

AL14

Operating hours - flow fans

Manu*¹

Display

-

AL15

Operating hours - return fan

Manu*¹

Display

-

AL16

Operating hours - coil 1 pump

Manu*¹

Display

-

AL17

Operating hours - coil 2 pump

Manu*¹

Display

-

AL18

Room temperature probe/return broken

or disconnected

Auto

Inhibits the controls upon

which the sensor is dependent

Configurable

AL19

Discharge air temperature sensor broken

or disconnected

Auto

Inhibits the controls upon

which the sensor is dependent

Configurable

AL20

Outdoor air temperature sensor broken or

disconnected

Auto

Inhibits the controls upon

which the sensor is dependent

Configurable

AL21

Room humidity probe/return broken or

disconnected

Auto

Inhibits the controls upon

which the sensor is dependent

Configurable

AL22

Exhaust air temperature sensor broken or

disconnected

Auto

Inhibits the controls upon

which the sensor is dependent

Configurable

AL23

Channel

pressure

probe

broken

or

disconnected

Auto

Inhibits the controls upon

which the sensor is dependent

Configurable

AL24

Air quality probe broken or disconnected

Auto

Inhibits the controls upon

which the sensor is dependent

Configurable

AL25

Flow

humidity

sensor

broken

or

disconnected

Auto

Inhibits the controls upon

which the sensor is dependent

Configurable

AL26

Remote set point variator potentiometer

broken or disconnected

Auto

Inhibits the controls upon

which the sensor is dependent

Configurable

AL27

Dampers opening potentiometer broken

Auto

Inhibits the controls upon

Configurable