6.16.3

Enabling Free-Cooling / Free-Heating in temperature

The free-cooling in temperature, if enabled (PS01=1), can be activated when the difference between the room air

temperature and the outdoor air temperature reaches the Set point which has been set (parameter PS13) and relative

hysteresis (parameter PS12).

The free-cooling in temperature, if enabled (PS01=1), can be activated when the difference between the room air

temperature and the outdoor air temperature reaches the Set point which has been set (parameter PS13) and relative

hysteresis (parameter PS12).

Note: it is necessary to enable the utilization of the outdoor air temperature sensor (PH40=1). If the sensor is in error

the control is disabled.

6.16.4

Free-Cooling and Free-Heating Control

The control of the free-cooling/free-heating commands the opening of the outdoor air shutter.

When free-cooling/free-heating conditions exist; or if the control can be enabled (and the request is greater than zero)

the ramps which command the heating/cooling are split into two successive ramps, the first (half the differential)

regulates the free-cooling/free-heating using the outdoor air shutter, the second regulates the heating/cooling valves.

SUMMER operation/COOLING: Free-Cooling

PS12:

T.

Room

T.

T. Outdoor – T.

PS13:SetF

PS12:

PS13:SetF

Enable Free-Cooling in temperature

Enable Free-Heating in temperature

Set Point

Supply

T. Supply

Pb01

Pb01 /

NY

Pb03

100 %

0 %

Cooling coil

Outdoor

air

dampers

regulated in free-cooling