EVCO S.p.A.

c-pro 3

NODE kilo AHU | Application manual ver. 1.0

page 32 of 114

PS21:

Differential – Air Quality Control

100

0

2000

ppm

IS-SE

HEAT RECOVERY DEVICE

Pr01

Differential Set Point for control of heat

exchanger

5.0

0.0

20.0

°C

IS-RH

Pr02

Differential of control of heat exchanger 3.0

0.0

20.0

°C

IS-RH

Pr03

Minimum

Set

Point

expulsion

temperature

1.0

PH03

PH04

°C

IS-RH

Pr04

Differential

minimum

expulsion

temperature

4.0

0.0

20.0

°C

IS-RH

Pr05

By pass cycle time of heat exchangers

at cross flow for melting

5

1

99

Min

IS-RH

Pr07

Minimum velocity of rotating heat

exchanger velocity

0.0

0.0

Pr08

%

IS-RH

Pr08

Maximum velocity of rotating heat

exchanger velocity

100.0

Pr07

100.0

%

IS-RH

PUMP

Menu accessible only if PG10=1 or

PG11=1

PP01

Types of pump control

0: Continuous adjustment

1: Control On/Off

0

0

1

-

IS-P

PP02

Set Point on the control ramp for pump

start-up

5.0

PP03

90.0

%

IS-P

Only

if

PP01=1

PP03

Set Point on the control ramp for pump

shutdown

2.0

1.0

PP02

%

IS-P

PP04

Wait time for pump shutdown (only

with PP01=1)

10

1

99

Min

IS-P

OFF

Unit

immediat

ely shuts

down

pump

PROTECTION DEVICE

PA01

Enable alarms during hours of fan

operation

YES (1)

NO (0)

YES (1)

-

IS-S

PA02

Enable alarms during hours of pump

operation

NO (0)

NO (0)

YES (1)

-

IS-S

PA03

Signal alarms during hours of operation

on alarm relay

YES (1)

NO (0)

YES (1)

-

IS-S

PA04

Sensor alarm delay

10

0

240

Sec

IS-S

PA05

Signal alarm sensor on alarm relay

YES (1)

NO (0)

YES (1)

-

IS-S

PA09

Signal fan alarms on alarm relay

YES (1)

NO (0)

YES (1)

-

IS-S

PA16

Signal alarms thermal pumps on alarm

relay

YES (1)

NO (0)

YES (1)

-

IS-S

PA20

Type of pressure switch alarm re-arm

(heat recovery device)

0: Auto - Automatic

1: Manu - Manual

Manu

(1)

Auto

(0)

Manu

(1)

-

IS-S