beautypg.com

6regulations, 1 machine status – EVCO EPK4BHQ1AH Installer manual User Manual

Page 45

background image

EVCO S.p.A.

c-pro 3

NODE kilo AHU | Application manual ver. 1.0

page 45 of 114

6

Regulations

6.1

Machine status

Several procedures exist for switching the unit ON and OFF:

Using the dedicated ON/OFF key (this function is enabled via parameter PH05).

Switching ON – Press the dedicated key for about 2 seconds: If all other enabled functions are present,

the machine will switch on by itself

Switching OFF – Press the dedicated key for about 2 seconds: the machine switches itself OFF.

Using the ON/OFF command from digital input (this function is enabled via parameter PH07).

Switching ON – Close the remote ON/OFF contact: If all other enabled functions are present,

the machine will switch on by itself

Switching OFF – If the remote ON/OFF contact reveals itself to be open, the machine switches itself “OFF from

digital input, indicated by “OFF D”.

Using a supervisory protocol (this function is enabled via parameter PH09).

Switching ON – Activate via protocol the switching ON status: If all other enabled functions are present,

the machine will switch on by itself

Switch-off – if switch-on status is deactivated from protocol, the machine will switch-off from

supervision protocol, indicated by “OFF S”.

Using a schedule (this function is enabled via parameter PH04).

Switching ON – If the date and time of the RTC indicates an ON status: if all other enabled functions are

present, the machine switches itself ON.

Switching OFF – If the date and time of the RTC indicates an OFF status; the machine switches itself OFF.

OFF statuses from digital input, supervisory protocol and schedule are only accessible if the machine has been enabled

by key press.

The machine ON/OFF key is the ESC key.