beautypg.com

21 time schedule, 22 miscellaneous management, 3 variation set point from supervisor – EVCO EPK4BHQ1AH Installer manual User Manual

Page 94: 4 manual fan operation, 1 last date of maintenance, 2 restore default parameters

background image

EVCO S.p.A.

c-pro 3

NODE kilo AHU | Application manual ver. 1.0

page 94 of 114

6.20.3

Variation set point from supervisor

The program provides the possibility to manage a parameter OS02 Offset Set point from Supervisor which, based on the

status set by the supervisor, sums an offset at the control Set point. To enable this function set the parameter PH26 Enable

variation Set point from supervisor and set to one the related variable from supervisor.

Note: the offset is summed at the current value of the Set point and not that which is defined by the parameter; this

indicates that the Set point could have already been modified due to other interventions: time zone, variations by Digital

inputs.

6.20.4

Manual fan operation

In this status the devices do not participate in thermo control; they are however sensitive to eventual alarms. Manual

operation (or operating less than the two flow and return fans) is guaranteed by parameter PM20.

If value set to 0 (Auto) this will define normal device behaviour

If value set to 1 (Manu) this will disable the fans and bring them to manual operation

Fans operating manually do not participate in controls and can be forced into operation using parameter PM21.

If the fans are the On/Off type they may be forced on by simply setting any value greater than 0.0% at parameter

PM21. If the fans are in modulating control, and therefore at inverter with parameter PM21, it is possible to set the

speed which must be maintained during the test phase. In each case where the value is 0.0% the fans will remain off.

While operating manually the fans will always be sensitive to alarms and related consequences. In order to restore at

the control you will need to reset parameter PM20 to the value “Auto” (Automatic).

6.21

Time schedule

The real time clock allows the operator to define a weekly schedule for the unit.

Three different time bands (T1/T2/T3) can be defined. Each time band have a set point offset to adjust the actual

control set point.

Each day of the week can have 3 time bands, every band has an hour of start, and this band continue till next valid

band of the same day, or other days.

If the RTC is in alarm or disabled, the function becomes inhibited.

6.22

Miscellaneous management

6.22.1

Last date of maintenance

In the Menu Maintenance Operator->Operation you will find a page with the ability to memorize the last date of

maintenance for the plant. By pressing on “Update” the old date which is in the system will automatically be updated

with the new correct date; updating the maintenance date can be done at parameter PM90.

6.22.2

Restore default parameters

Using the “Parameter resetting” procedure, all system parameters can be reset to their original default values. After

entering the InSt->MAP menu – which is only accessible while the machine is switched OFF – set parameter PH15=1

and wait for the “0” value to reappear on the display; the system will automatically reset all parameters back to their

default values.

After this operation, it is necessary to power down the machine and then power it up again, to avoid the risk of

malfunctions.