page 52 of 114
6.7
Setting the RTC
When the power supply is disconnected from the controller for a few days, the RTC (Real Time Clock) system clock
loses its time. When the controller power is up again, it requires setting the correct date and time. In this case, upon
machine start-up the following page will appear allowing to set the time:
SET CLOCK DATE&TIME
17/06/2008 10:53:43
OK
Once the clock has been configured, press OK to update the RTC time. The main application page will be shown.
Pressing OK to confirm the reset of the clock alarm (ERTC) at which point the conditions of the alarm has been
restored.
In case the alarm doesn’t disappear: remove and reconnect the power of the controller and then manually reset the
alarm.
Note: This function is enabled only if the parameter PG03=1, that is, if the system clock is enabled.
6.8
Plant set-up
6.8.1
Set-up of the heat recovery device
The screens that allow to configure the plant are shown below graphically
Screen from where it is possible to set the SETUP of the heat recovery device, confirming the activation via "Yes" or
deactivation with "No".
6.8.2
Set-up of the fans