EVCO S.p.A.

c-pro 3

NODE kilo AHU | Application manual ver. 1.0

page 35 of 114

PH26

Enable variation Set Point as Supervisor

NO (0)

NO (0)

YES (1)

-

IS-V

PH27

Enable distinct/single Set Point for

heating/cooling:

0: Distinct set point

1: Unique set point

0

0

1

-

IS-V

If PH27=1

(single Set

Point), the

single Set

Point

utilized for

control

and SEtH.

PH32

Unit of measurement of temperature:

0: °Celsius

1: °Fahrenheit

0 (°C)

0 (°C)

1 (°F)

-

IS-V

PH33

Unit of measurement of pressure:

0: Bar

1: psi

0 (Bar)

0 (Bar)

1 (psi)

-

IS-V

PH34

Language:

0: English

1: Italian

0 (Bar)

0 (Bar)

1 (psi)

-

IS-V

PH37

PPM

transducer

minimum

value

CO2/VOC

0

0

10000

ppm

IS-V

PH38

PPM

transducer

maximum

value

CO2/VOC

2000

0

10000

ppm

IS-V

PH40

Type of return temperature sensor

0: PTC

1: NTC

2: PT1000

3: NTC 10K-2

4: NTC 10K-3

1

0

4

-

IS-V

PH41

Type of flow temperature sensor

0: PTC

1: NTC

2: PT1000

3: NTC 10K-2

4: NTC 10K-3

1

0

4

-

IS-V

PH42

Type of external temperature sensor

0: PTC

1: NTC

2: PT1000

3: NTC 10K-2

4: NTC 10K-3

1

0

4

-

IS-V

PH43

Type of return/environment humidity

sensor

0: 0-20mA

1: 4-20mA

2: 0-5V

3: 0-10V

3

0

3

-

IS-V