EVCO EPK4BHQ1AH Installer manual User Manual
Page 35

EVCO S.p.A.
c-pro 3
NODE kilo AHU | Application manual ver. 1.0
page 35 of 114
PH26
Enable variation Set Point as Supervisor
NO (0)
NO (0)
YES (1)
-
IS-V
PH27
Enable distinct/single Set Point for
heating/cooling:
0: Distinct set point
1: Unique set point
0
0
1
-
IS-V
If PH27=1
(single Set
Point), the
single Set
Point
utilized for
control
and SEtH.
PH32
Unit of measurement of temperature:
0: °Celsius
1: °Fahrenheit
0 (°C)
0 (°C)
1 (°F)
-
IS-V
PH33
Unit of measurement of pressure:
0: Bar
1: psi
0 (Bar)
0 (Bar)
1 (psi)
-
IS-V
PH34
Language:
0: English
1: Italian
0 (Bar)
0 (Bar)
1 (psi)
-
IS-V
PH37
PPM
transducer
minimum
value
CO2/VOC
0
0
10000
ppm
IS-V
PH38
PPM
transducer
maximum
value
CO2/VOC
2000
0
10000
ppm
IS-V
PH40
Type of return temperature sensor
0: PTC
1: NTC
2: PT1000
3: NTC 10K-2
4: NTC 10K-3
1
0
4
-
IS-V
PH41
Type of flow temperature sensor
0: PTC
1: NTC
2: PT1000
3: NTC 10K-2
4: NTC 10K-3
1
0
4
-
IS-V
PH42
Type of external temperature sensor
0: PTC
1: NTC
2: PT1000
3: NTC 10K-2
4: NTC 10K-3
1
0
4
-
IS-V
PH43
Type of return/environment humidity
sensor
0: 0-20mA
1: 4-20mA
2: 0-5V
3: 0-10V
3
0
3
-
IS-V