NODE kilo AHU | Application manual ver. 1.0

page 72 of 114

6.10.7

Minimum/Maximum discharge temperature

When the discharge temperature exceeds the maximum or minimum set of parameters PF16 or PF17 the ventilation is

disabled.

PF15: Enable fan limitation

PF16: Min. temperature of limitation

PF17: Max. temperature of limitation

PF18: Differential

6.10.8

"Intake cycles"

When the temperature control sensor is positioned in the return duct (PG05=1), it is necessary to activate periodically

the return fan in order to measure the room temperature (parameter PC05 to enable).

The cycle is composed of a wait time (PC06) during which the fan remains off as well as a wait time for activation

(PC07) in which the fans will turn on. The cycle always begins with a period of pause; as soon as the fan is shut down

from the control room temperature (satisfactory room temperature), the cycle will terminate if during the activation

phase the regulation ramp of the ambient temperature exceeds the activation point of the fan. With the parameter

PC08 you can decide whether to activate only the pickup fan (PC08=0) or both the return and flow fans (PC08=1)

during air quality control measuring.

Note 1: if the fan control is continuous (PF01=0) the air quality sensor cycle can never be activated and is thus

unusable. If the return fan is not present (PG09=0) this function cannot be used.

Note 2: the fan activation time during the cycle (PC07) must be sufficiently long with respect to the protection time of

the two fans (PF05), to ensure that both fans are able to turn on during the start-up of the air quality measuring

phase (if requested, see PC08).

T.discharge

Set

Set Max -

Set Min

Set Min +

OFF

ON

Enable Fans