EVCO EPK4BHQ1AH Installer manual User Manual
Page 30

EVCO S.p.A.
c-pro 3
NODE kilo AHU | Application manual ver. 1.0
page 30 of 114
Pb24
Differential for midseason control
3.0
0.0
10.0
°C
IS-B
Pb25
Minimum value for modulating output
resistances
0.00
0.00
100.00
%
IS-B
Pb30
Enable flow limitation
0: Disabled
1: Heating
2: Cooling
3: Enabled
3
0
3
IS-B
Pb31
Cooling limitation set point
10.0
-15.0
70.0
°C
IS-B
Pb32
Cooling limitation differential
5.0
0.0
30.0
°C
IS-B
Pb33
Cooling limitation minimum value
0.0
0.0
100.0
%
IS-B
Pb34
Heating limitation set point
30.0
-15.0
70.0
°C
IS-B
Pb35
Heating limitation differential
5.0
0.0
30.0
°C
IS-B
Pb36
Heating limitation minimum value
0.0
0.0
100.0
%
IS-B
HUMIDIFIER
PU02:
Neutral zone humidity control
6
0
100
%
IS-U
PU03
Differential for the control of humidity
10
0
100
%
IS-U
PU04
Integral
time
for
the
control
of
dehumidification (with cold coil)
0
0
999
Sec
IS-U
If
PU04=0
integral
action
not
present
PU05
Enable
functional
limit
for
the
dehumidification
NO (0)
NO (0)
YES (1)
-
IS-U
PU06
Sensor for the control of humidity:
0: Environment/return
1: Flow
0
0
1
-
IS-U
PU10
Enable humidifier control with return
temperature
YES (1)
NO (0)
YES (1)
-
IS-U
PU11
Set Point on the return temperature to
enable the humidifier
22.0
PH03
PH04
°C
IS-U
Only
if
PU10=1
PU12
Differential on the return temperature
to enable the humidifier
3.0
0.0
20.0
°C
IS-U
Only
if
PU10=1
PU13
Enable maximum discharge air humidity
control
YES (1)
NO (0)
YES (1)
-
IS-U
PU14
Maximum discharge air humidity set
point
80
0
95
%
IS-U
PU15
Hysteresis
maximum
discharge
air
humidity control
20
0
40
%
IS-U
PU16
Minimum
value
for
modulating
humidifier output
0.00
0.00
100.00
%
IS-U
PU17
Enable winter dehumidification:
0: function is not enabled
1: function enabled
1
0
1
-
IS-U
PU18
Set-point for the management winter
dehumidification
55
0
100
%
UT